Analisa Harmonisa Pada Unit Crane RTG (Rubber Tyred Gantry) Di PT. Nilam Port Terminal Indonesia
DOI:
https://doi.org/10.56795/fortech.v4i1.4102Keywords:
RTG (Rubber Tyred Gantry) Crane, Variable Speed Drive (VSD), Harmonic Distortions, Harmonic FilterAbstract
RTG (Rubber Tyred Gantry) Crane tends to have harmonic distortions. It is caused by the VSD switching process that converts current from DC to AC, decreasing the power quality and affecting power generation. Disturbance tends to happen on voltage or a current sine wave of the system that contains multiplied frequency from fundamental frequency. It is required to analyze based on the IEEE standard of Std 519-2014 which described that the 20kV bus voltage has a limit value of 3% for VIHD and 5% for VTHD. By using available software, simulation is applied to the RTG Crane electrical system. Harmonic distortion will be discussed by gathering simulation result data in the form of the harmonic spectrum and harmonic wave. harmonic filter to be applied is an Active Filter and Passive Filter that then compared the compatibility to solve the harmonic distortion. The analysis is also applied to Power Factor (PF) value changes before and after filter installation.
References
Sugiarto,Hadi.2012.”Kajian Harmonisa Arus Dan Tegangan Listrik di Gedung Administrasi Politeknik.
Putra N P U, "Harmonic Effect for Voltage Stability Condition in Radial Distribution System", 2019 International Seminar on Intelligent Technology and Its Applications, DOI: 10.1109/ISITIA.2019.8937215
R Sulistyowati , D Widiatmoko , H A Sujono ,2021" Harmonics Analysis of Inverter Circuits on Smart Grid System, ICATECH.
Rosa, F.C.D.L. 2006 Harmonic And Ppower System. USA: Taylor & Francis Group, LLC.
Bukit, F.R.A. 2017. Analisa HarmonisapppPadakkKarakteristik Motor Induksi Tiga Phasa. Juitech / Vol.01 / No. 02 / Oktober 2017 / pISSN : 2580-40570/ e-ISSNn: 2597-7261
Budi, A.I.P, dkk. 2018. Analisis Pemasangan Filter Pasif Dan Aktif Terhadap Kandungan Harmonisa Dan Rugi-Rugi Daya Gardu Distribusi KA 2085 Di PT. PLN (Persero) Distribusi Bali Rayon Mengwi. E-Jurnal SPEKTRUM Vol. 5, No. 1 Juni 2018
Ray Ridley. (Nov. 2006). Analyzing the SEPIC converter. Power Systems Design Europe [Online]. Available:http://www.powersystemsdesign.com/design_ tips_nov06.pdf
Robert W. Erickson and Dragan Maksimovic, Fundamentals of Power Electronics, 2nd ed. (New York: Springer Science+Business Media LLC, 2001).
John Betten and Robert Kollman. (Jan. 25, 2006). No need to fear: SEPIC outperforms the flyback. Planet Analog[Online].Available:http://www.planetanalog.com/ showArticle.jhtml?articleID=177103753.
ETAP Harmonic Analysis. 2005.